Enhanced Tube Fouling Under Cooling Water Conditions

Edward S. Beardwood, George F. Hays, Steven J. Colby

Abstract

Fouling of enhanced heat exchanger tubes has been a significant problem in the industry since their
introduction. The intensity of fouling has been shown to be a function of the number of flutes present in
the enhanced tube.1,2,3 Field and laboratory data indicate that enhanced tubes biofoul more rapidly and to higher fouling factors than do traditional smooth tubes. Enhanced tubes have also been found to clean-up more rapidly than smooth tubes when comparable cleaning programs are employed. The enhanced tube is less susceptible to insitu inorganic crystallization fouling than a smooth tube.

A novel monitor has been developed to evaluate biomass deposition and removal under operating heat
exchanger conditions utilizing an enhanced tube test section. It has also been found that traditional
oxidizing biocides are relatively inefficient in the removal of biofilm from enhanced tubes. The use of
biodispersants in conjunction with oxidizing biocides has demonstrated a significant reduction in enhanced tube biofouling. This paper will review prior research and present findings from recent pilot cooling system studies.

Key words: enhanced heat exchanger tubes, inorganic crystallization fouling, annular heat transfer test section,biofouling, biodispersants, oxidizing biocides, bromine, chlorine, chlorine dioxide, biofilm monitoring.

Please sign in
to download the full paper.
Not registered yet? Follow this link
By registering, you agree to receive communications from Arthur Freedman Associates. You may opt-out at any time.
Arthur Freedman Associates
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.